Standard

Heat transfer intensification in emergency cooling heat exchanger and dry cooling towers on nuclear power plant using air-water mist flow. / Abed, Akram h.; Shcheklein, Sergey E.; Pakhaluev, Valery M.
в: Nuclear Energy and Technology, Том 5, № 4, 2019, стр. 281-287.

Результаты исследований: Вклад в журналСтатьяРецензирование

Harvard

APA

Vancouver

Author

BibTeX

@article{de02d2231aab45518fd43c0452eb06d5,
title = "Heat transfer intensification in emergency cooling heat exchanger and dry cooling towers on nuclear power plant using air-water mist flow",
abstract = "Advanced nuclear power plants are equipped with passive emergency heat removal systems (PEHRS) for removing the decay heat from reactor equipment in accidents accompanied by primary circuit leakage to the final heat absorber (ambient air). Herein, the intensity of heat dissipation to air from the outer surface of the heat exchanger achieved by buoyancy induced natural convection is extremely low, which need to a large heat exchanger surface area, apply different types of heat transfer intensification including (grooves, ribs and extended surfaces, positioning at higher altitudes, etc.). The intensity of heat removal is also strongly dependent on the ambient air temperature (disposable temperature head). Construction of nuclear power plants in countries with high ambient temperatures (Iran, Bangladesh, Egypt, Saudi Arabia, and others) which are characterized by a high level of ambient temperature imposes additional requirements on the increase of the heat exchange surfaces. The experimental investigation results of heat transfer intensification by a low energy ultrasonic which supply a fine liquid droplet (size ~3 µm) in the cooling air are presented in the present paper. In such case, the heat transfer between the surface and cooling flow involves the following three physical effects: convection, conductive heat transfer, and evaporation of water droplets. The last two effects weakly depend on the ambient air temperature and provide an active heat removal in any situation. The investigation was performed using a high-precision calorimeter with a controlled rate of heat supply (between 7800 and 12831 W/m2) imitating heated surface within the range of Reynolds numbers from 2500 to 55000 and liquid (water) flow rates from 23.39 to 111.68 kg·m-2·h-1. The studies demonstrated that the presence of finely dispersed water results in a significant increase in heat transfer compared with the case of using purely air-cooling. With a fixed heat flux, the energy efficiency increases with increasing water concentration, reaching the values over 600 W·m-2·C-1 at 111.68 kg·m-2·h-1, which is 2.8 times higher than for air cooling. With further development of research in order to clarify the optimal areas of intensification, it is possible to use this technology to intensify heat transfer to the air in dry cooling towers of nuclear power plants and thermal power plants used in hot and extreme continental climates.",
author = "Abed, {Akram h.} and Shcheklein, {Sergey E.} and Pakhaluev, {Valery M.}",
note = "The present study was implemented under the financial support in pursuance with Resolution No. 211of the Government of the Russian Federation under Contract No. 02.A03.21.0006.",
year = "2019",
doi = "10.3897/nucet.5.47972",
language = "English",
volume = "5",
pages = "281--287",
journal = "Nuclear Energy and Technology",
issn = "2452-3038",
publisher = "Национальный исследовательский ядерный университет {"}МИФИ{"}",
number = "4",

}

RIS

TY - JOUR

T1 - Heat transfer intensification in emergency cooling heat exchanger and dry cooling towers on nuclear power plant using air-water mist flow

AU - Abed, Akram h.

AU - Shcheklein, Sergey E.

AU - Pakhaluev, Valery M.

N1 - The present study was implemented under the financial support in pursuance with Resolution No. 211of the Government of the Russian Federation under Contract No. 02.A03.21.0006.

PY - 2019

Y1 - 2019

N2 - Advanced nuclear power plants are equipped with passive emergency heat removal systems (PEHRS) for removing the decay heat from reactor equipment in accidents accompanied by primary circuit leakage to the final heat absorber (ambient air). Herein, the intensity of heat dissipation to air from the outer surface of the heat exchanger achieved by buoyancy induced natural convection is extremely low, which need to a large heat exchanger surface area, apply different types of heat transfer intensification including (grooves, ribs and extended surfaces, positioning at higher altitudes, etc.). The intensity of heat removal is also strongly dependent on the ambient air temperature (disposable temperature head). Construction of nuclear power plants in countries with high ambient temperatures (Iran, Bangladesh, Egypt, Saudi Arabia, and others) which are characterized by a high level of ambient temperature imposes additional requirements on the increase of the heat exchange surfaces. The experimental investigation results of heat transfer intensification by a low energy ultrasonic which supply a fine liquid droplet (size ~3 µm) in the cooling air are presented in the present paper. In such case, the heat transfer between the surface and cooling flow involves the following three physical effects: convection, conductive heat transfer, and evaporation of water droplets. The last two effects weakly depend on the ambient air temperature and provide an active heat removal in any situation. The investigation was performed using a high-precision calorimeter with a controlled rate of heat supply (between 7800 and 12831 W/m2) imitating heated surface within the range of Reynolds numbers from 2500 to 55000 and liquid (water) flow rates from 23.39 to 111.68 kg·m-2·h-1. The studies demonstrated that the presence of finely dispersed water results in a significant increase in heat transfer compared with the case of using purely air-cooling. With a fixed heat flux, the energy efficiency increases with increasing water concentration, reaching the values over 600 W·m-2·C-1 at 111.68 kg·m-2·h-1, which is 2.8 times higher than for air cooling. With further development of research in order to clarify the optimal areas of intensification, it is possible to use this technology to intensify heat transfer to the air in dry cooling towers of nuclear power plants and thermal power plants used in hot and extreme continental climates.

AB - Advanced nuclear power plants are equipped with passive emergency heat removal systems (PEHRS) for removing the decay heat from reactor equipment in accidents accompanied by primary circuit leakage to the final heat absorber (ambient air). Herein, the intensity of heat dissipation to air from the outer surface of the heat exchanger achieved by buoyancy induced natural convection is extremely low, which need to a large heat exchanger surface area, apply different types of heat transfer intensification including (grooves, ribs and extended surfaces, positioning at higher altitudes, etc.). The intensity of heat removal is also strongly dependent on the ambient air temperature (disposable temperature head). Construction of nuclear power plants in countries with high ambient temperatures (Iran, Bangladesh, Egypt, Saudi Arabia, and others) which are characterized by a high level of ambient temperature imposes additional requirements on the increase of the heat exchange surfaces. The experimental investigation results of heat transfer intensification by a low energy ultrasonic which supply a fine liquid droplet (size ~3 µm) in the cooling air are presented in the present paper. In such case, the heat transfer between the surface and cooling flow involves the following three physical effects: convection, conductive heat transfer, and evaporation of water droplets. The last two effects weakly depend on the ambient air temperature and provide an active heat removal in any situation. The investigation was performed using a high-precision calorimeter with a controlled rate of heat supply (between 7800 and 12831 W/m2) imitating heated surface within the range of Reynolds numbers from 2500 to 55000 and liquid (water) flow rates from 23.39 to 111.68 kg·m-2·h-1. The studies demonstrated that the presence of finely dispersed water results in a significant increase in heat transfer compared with the case of using purely air-cooling. With a fixed heat flux, the energy efficiency increases with increasing water concentration, reaching the values over 600 W·m-2·C-1 at 111.68 kg·m-2·h-1, which is 2.8 times higher than for air cooling. With further development of research in order to clarify the optimal areas of intensification, it is possible to use this technology to intensify heat transfer to the air in dry cooling towers of nuclear power plants and thermal power plants used in hot and extreme continental climates.

UR - http://www.scopus.com/inward/record.url?partnerID=8YFLogxK&scp=85144673321

U2 - 10.3897/nucet.5.47972

DO - 10.3897/nucet.5.47972

M3 - Article

VL - 5

SP - 281

EP - 287

JO - Nuclear Energy and Technology

JF - Nuclear Energy and Technology

SN - 2452-3038

IS - 4

ER -

ID: 51596286